芬兰Powernet 电源 后备电源 DC UPS不间断电源 VIDI系列
VIDI+系统控制器
VIDI+ I/O 系统控制器
UIF,用户界面显示
VIDI-LVD 低压隔离开关
VIDI-BM 电池监测
VIDI-SAM 串行适配器模块
VIDI 控制器平台适用于 OPUS 直流电源系统。 它为直流电源系统管理提供智能且简单的用户界面和全面的功能集。
VIDI 架构基于 PowerCAN 总线通信和模块化设计,可实现出色的系统可扩展性、可选的附加功能和设计灵活性。
适用于所有 24 VDC 至 220 VDC OPUS DC 电源系统的通用控制器
模块化结构可实现最佳性能和设计灵活性
复杂的用户界面。 用户友好的本地和远程操作
全面的功能和警报
众多用户可配置的警报和设置
通过 RS232、调制解调器或 TCP/IP 使用 WEB 界面进行全面远程监控
Technical Specifications, Advanced Controller Modules
Electrical | VIDI+ , VIDI+ I/O |
Power Input voltage range | 18 – 280 VDC |
Communication Ports | VIDI+ , VIDI+ I/O |
LAN | 10/100 Ethernet, RJ-45 connector |
Serial communication | RS-232, 9600-115200 kbps |
Monitoring and Control Local Monitoring and Control | User Interface Module |
Local Display | 128 x 64 Graphical LCD with Backlight |
Local Operation | Dial button, Info button and cancel button |
Local LED indication | 3 color system Status LED |
Info | Dedicated button to open info text |
Default view | Charge mode, system voltage, number of active alarms |
Languages | English, Russian, Finnish, Custom |
Monitoring and Control Remote Monitoring and Control | VIDI+ , VIDI+ I/O |
Remote PC connection | Connect via LAN |
Local PC connection | Connect directly with serial port RS-232 or LAN port |
Alarms | E-mail or SNMP traps |
Remote user interface | Web interface, 4 access levels |
Remote terminal | Text mode interface over Telnet/SSH |
Supported Protocols | HTTP, HTTPS, Telnet, SSH, SMTP, SNMPv2, SNMPv3 NTP, DHCP, Modbus TCP/IP |
Languages | English, Russian, Finnish |
System Features | VIDI+ , VIDI+ I/O | |
Measurements | System Output Voltage Measurement AC input voltage, individual rectifiers DC output voltage, individual rectifiers DC output current, individual rectifiers Temperature, individual rectifiers DC output current, total rectifiers Battery current Load current | |
Functions | PowerCAN-Bus interface to MRC rectifiers and Smart Peripheral Modules | |
Energy Save Mode, with MRC rectifiers | ||
Rectifier runtime counter | ||
Alarm configuration | ||
System parameters upload and download in XML format | ||
Real Time Clock with Battery Backup | ||
Plug-and-Play Support, Automatic Module Configuration | ||
Inventory Management for Installed Modules | ||
Site Information text input | ||
Connections | VIDI+ , VIDI+ I/O | |
Battery or load LVD | 1 pcs Contactor Coil Driver, Aux contact | |
Connections | VIDI+ | VIDI+ I/O |
Alarm/Temperature Inputs | 4 | 12 |
Alarm Relay Outputs | 4 | 12 |
Earth fault detection | 0 | 1 |
Modules | VIDI+ , VIDI+ I/O | |
Supported max number of all modules | 48 |
Limitations per module types | VIDI+ , VIDI+ I/O |
Local User Interface panel | 1 |
Rectifiers, supported max amount | 47 |
VIDI-LVD Low voltage disconnection modules. Supported max amount. | 8 |
VIDI-BM Battery management modules. Supported max amount. | 16 |
VIDI-SAM modules. Supported max amount. | 1 |
Battery Management features Measurements | VIDI+ , VIDI+ I/O |
Battery tests | Manual battery test Periodic battery test Natural battery tests, starts on mains fault |
Charge modes | Float charge Manual boost charge Periodic boost charge Automatic boost charge Temperature compensation in all charge modes |
Functions | Charge current limiting Discharged Ah-counter Time window for battery tests |
Alarms | VIDI+ , VIDI+ I/O |
Configurable | Mains Fault Phase Fault Rectifier Low/Over voltage System Low/Over voltage Rectifier overcurrent Rectifier Over Temperature System Over Temperature High Battery Temperature Low Battery Temperature Rectifier Fault Module Communication Error/Module Fault Load fuse fault Battery LVD or Load LVD Contactor failure Battery Temperature Sensor Fault Rectifiers No Redundancy Alarms/Rectifiers Over Load, Configurable limits Load Disconnect Warning, Configurable limits Load Disconnect Battery Fuse Fault Battery Discharge Test Fault Boost Charge Fault Battery Disconnect Warning, Configurable limit |
Alarms | VIDI+ I/O |
Configurable | Earth fault detection |
Log data | VIDI+ , VIDI+ I/O |
Alarm log: 512 last alarms, Event log: 100 last events, Battery Temperature Log Graph, System Power log, 12 Months |
Connectors | VIDI+ , VIDI+ I/O |
Alarm/Temperature input | Screw terminals |
Internal PowerCAN-Bus connector | User interface Module RJ11 Other PowerCAN connectors RJ45 |
PowerCAN Termination Plug | RJ45 Plug |
Technical Specifications VIDI-LVD Low Voltage Disconnect Module
Electrical | VIDI-LVD |
Power Input voltage range | 18 – 280 VDC |
Communication | PowerCAN connection to VIDI+ Controller |
Coil Contact Driver | Maximum allowed continuous coil current: 2A |
Coil Driver output voltage | System voltage |
Aux contact for contactor | Indication of the actual core poSITIon of the latched contactor |
System voltage measurement range | 0 – 280 VDC |
Current Sense | 1 pc shunt voltage measurement, 60 mV |
Alarm inputs | 2 pcs configurable alarm/temperature inputs |
Status indication | LED Green/Red |
Mechanical data | Dimensions (H xW x D) : 75 x 160 x 27 mm Weight : 320 g Protection class IP20 |
Technical Specifications VIDI-BM Battery Monitoring Module
Electrical | VIDI-BM |
Power Input voltage range | 18 – 280 VDC |
Communication | PowerCAN connection to VIDI+ Controller |
Block Voltage Measurement | Inputs: 4 pcs 12V nominal, Accuracy < 20mV, polarity protection |
System voltage measurement range | 0 – 280 VDC |
Current Sense | 1 pc shunt voltage measurement, 60 mV |
Alarm inputs | 2 pcs configurable alarm/temperature inputs |
Status indication | LED Green/Red |
Mechanical data | Dimensions (H xW x D) : 75 x 160 x 27 mm Weight : 320 g Protection class IP20 |
Technical Specifications VIDI-SAM Serial Adapter Module
Electrical | VIDI-SAM |
Power Input voltage range | 18 – 280 VDC |
Communication | PowerCAN connection to VIDI+ Controller |
Auxiliary communications | RS-232, RS-485, CAN |
System voltage measurement range | 0 – 280 VDC |
Current Sense | 1 pc shunt voltage measurement |
Alarm inputs | 2 pcs configurable alarm/temperature inputs |
Mechanical data | Dimensions (H xW x D) : 75 x 160 x 27 mm Weight : 320 g Protection class IP20 |
Technical Specifications, common
Environmental | VIDI+, VIDI+ I/O, VIDI-LVD, VIDI-BM, VIDI-SAM |
Cooling | Natural convection |
Acoustic noise | < 40 dB |
Operating temperature | -20 / +50 °C |
Storage temperature | -40 / +70 °C |
Humidity | 95 % (relative humidity, non-condensing) |
Altitude (max) | 2000 m above sea level |
Applicable Standards | |
EMC | Emissions: EN/IEC 61000-6-4 Immunity: EN/IEC61000-6-2 Harmonic currents: EN / IEC 61000-3-2 Voltage fluctuations & flicker: EN / IEC 61000-3-3 * Measured as a part of Opus C-series rack system |
Safety | IEC / EN 60950-1 * Tested as a part of Opus C-series rack system |
Order Information
System controller kits | |
Description | Order number |
VIDI+ controller kit. Includes system controller module and cable set | 8320X0004311 |
VIDI+ I/O controller kit. Includes system controller module and cable set | 8320X0004312 |
Auxiliary controller kits | |
Description | Order number |
VIDI BM kit. Includes Battery monitoring module and cable set | 9040X0002338 |
VIDI LVD kit. Includes Low Voltage Disconnector controller module and cable set. | 8320X0003275 |
VIDI SAM kit. Includes serial adapter module and cable set. Used with OPUS EIM and DUAL inverters. | 8320X0004402 |
本网页所展示的有关【芬兰Powernet 电源 后备电源 DC UPS不间断电源 VIDI系列】的信息/图片/参数等由的会员【 Powernet电源(Powernet电源充电器) 】提供,由智能装备网会员【 Powernet电源(Powernet电源充电器) 】自行对信息/图片/参数等的真实性、准确性和合法性负责,本平台(本网站)仅提供展示服务,交易前请与卖家联系,谨慎交易,因交易而产生的法律关系及法律纠纷由您自行协商解决,本平台(本网站)对此不承担任何责任。您在本网页可以浏览【芬兰Powernet 电源 后备电源 DC UPS不间断电源 VIDI系列】有关的信息/图片/价格等及提供 【芬兰Powernet 电源 后备电源 DC UPS不间断电源 VIDI系列】的商家公司简介、联系方式等信息。